Place of use
This type of cables is suıtable to use in machınary production, power stations, energy projects, conditioning-ventilation and other electrical systems, in dry and humid envıronments, especially in industrial environmental conditıons; with measuring, monitoring and controlling purposes. Halogen free cables have flame retardant properties and low smoke density.
Inner Conductor | Electrolytic Stranded Annealed Copper Wire, Class 2 |
Insulation | HFFR Compound EN 50290-2-26, |
Stranding | Cores Twisted in Layers |
Seperator | PES Tape |
Screen | Tinned Copper Wire Braiding |
Outer Sheath | HFFR Compound EN 50290-2-27, RAL 7001 Grey |
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C |
CONDUCTOR | INSULATION | CURRENT CARRYING | OPERATING | TEST | BENDING | TEMPERATURE | |||||||
mm² | Ω/km | MΩxKm | mm² | A |
|
|
|
|
|
|
| ||
0,75 | 26 | ≥ 20 | 0,75 | 13 | 300/500 V | 2000V | 7,5XD | -30ºC +70ºC | |||||
1,00 | 19,5 | 1,00 | 16 | ||||||||||
1,50 | 13,3 | 1,50 | 20 | ||||||||||
2,50 | 7,98 | 2,50 | 25 | ||||||||||
FLAME TEST | SMOKE DENSITY TEST | TEST ON CORROSIVENESS | HALOGEN | FLAME | |||||||||
IEC 60332-1-2 VDE 0482-332-1-2 EN 60332-1-2 | IEC 61034-2 | IEC 60754-2 VDE 0482-267-2-3 EN 50267-2-3 | IEC 60754-1 VDE 0482-267-2-1 EN 50267-2-1 | IEC 60332-3-24 VDE 0482-332-3-24 EN 60332-3-24 | |||||||||